1. Uhlobo lwesixhobo: uhlobo lwangaphandle
2. Ubushushu obuphakathi: ubushushu obuphezulu +40℃, ubushushu obuncinci -30℃
3. Ukuphakama: Iimitha ezili-1000 (>iimitha ezili-1000, ukunyuka kobushushu kufuneka kulungiswe)
4. Ubushushu obuhambelanayo: 90% (25℃)
5. Indawo yokufakelwa: akukho gesi irhabaxa, akukho mdaka ucacileyo kunye nezinye iindawo
Isiguquli samandla esilawula umbane esingaphazanyiswanga esine-110kV esinezigaba ezintathu
| Inikwe ingqikelelo umthamo (kVA) | Indibaniselwano yeVoltage kunye noluhlu lweTap | Ukudibanisa iqela Ileyibhile | Akukho mthwalo ilahleko kW(9) | Ukulahleka komthwalo kW(9) | Akukho mthwalo i-% yangoku | Intambo emfutshane ukuthintela % | |
| I-voltage ephezulu (kV) | Iphantsi i-voltage(kV) | ||||||
| 6300 | 110±2×2.5% 115±2×2.5% 121±2×2.5% | 6.3 6.6 10.5 | YNd11 | 5.90 | 33.0 | 0.50 | 10.5 |
| 8000 | 7.10 | 40.0 | 0.50 | ||||
| 10000 | 8.40 | 48.0 | 0.46 | ||||
| 12500 | 9.90 | 56.0 | 0.46 | ||||
| 16000 | 12.0 | 69.0 | 0.43 | ||||
| 20000 | 14.1 | 84.0 | 0.43 | ||||
| 25000 | 16.6 | 99.0 | 0.40 | ||||
| 31500 | 19.7 | 117 | 0.38 | ||||
| 40000 | 23.5 | 141 | 0.36 | ||||
| 50000 | 28.2 | 166 | 0.34 | ||||
| 63000 | 33.3 | 198 | 0.30 | ||||
| 75000 | 13.8 15.75 18 21 | 37.8 | 224 | 0.26 | 12~14 | ||
| 90000 | 43.5 | 258 | 0.24 | ||||
| 120000 | 54.2 | 320 | 0.22 | ||||
| 150000 | 64.1 | 379 | 0.19 | ||||
| 180000 | 72.0 | 434 | 0.16 | ||||
Phawula:
Indawo yokuthepha eyi-1. -5% ukuze ufumane amandla aphezulu okuthepha.
2. Kwi-boost transformer, kufanelekile ukusebenzisa isakhiwo esingenampompi. Ukuba kuyimfuneko ngokusebenza, i-tap ingamiselwa.
3. xa ireyithi yomthwalo wonyaka we-transformer iphakathi kwe-45%-46%, ixabiso lokulahleka elikwitheyibhile lingasetyenziselwa ukufumana ukusebenza okuphezulu.
Isiguquli samandla esilawula umbane esingaphazanyiswanga esinezigaba ezintathu se-6300kVA-63000kVA
| Umthamo olinganisiweyo (kVA) | Indibaniselwano yeVoltage kunye noluhlu lweTap | Ileyibhile yeqela elidibeneyo | Akukho lahleko lomthwalo kW(9) | Ukulahleka komthwalo kW(9) | Akukho mthwalo wangoku % | Impedance yesekethe emfutshane % | |
| I-voltage ephezulu (kV) | I-voltage ephantsi(kV) | ||||||
| 6300 | 110±2×2.5% 115±2×2.5% 121±2×2.5% | 6.36.610.5 | YNd11 | 5.90 | 33.0 | 0.50 | 10.5 |
| 8000 | 7.10 | 40.0 | 0.50 | ||||
| 10000 | 8.40 | 48.0 | 0.46 | ||||
| 12500 | 9.90 | 56.0 | 0.46 | ||||
| 16000 | 12.0 | 69.0 | 0.43 | ||||
| 20000 | 14.1 | 84.0 | 0.43 | ||||
| 25000 | 16.6 | 99.0 | 0.40 | ||||
| 31500 | 19.7 | 117 | 0.38 | ||||
| 40000 | 23.5 | 141 | 0.36 | ||||
| 50000 | 28.2 | 166 | 0.34 | ||||
| 63000 | 33.3 | 198 | 0.30 | ||||
| 75000 | 13.8 15.75 18 21 | 37.8 | 224 | 0.26 | 12~14 | ||
| 90000 | 43.5 | 258 | 0.24 | ||||
| 120000 | 54.2 | 320 | 0.22 | ||||
| 150000 | 64.1 | 379 | 0.19 | ||||
| 180000 | 72.0 | 434 | 0.16 | ||||
Isiguquli samandla sokulawula i-voltage yomthwalo esinezigaba ezintathu esiphindwe kabini esijikelezayo esine-6300kVA-63000kVA
| Umthamo olinganisiweyo (kVA) | Indibaniselwano yeVoltage kunye noluhlu lweTap | Ukudibanisa Ileyibhile yeqela | Akukho mthwalo ilahleko kW(9) | Ukulahleka komthwalo kW(9) | Akukho mthwalo i-% yangoku | Intambo emfutshane ukuthintela % | |
| Hi-voltage ye-igh(kV) | I-voltage ephantsi(kV) | ||||||
| 6300 | 110±8×1.25% | 6.3 6.6 10.5 21 | YNd11 | 6.4 | 33 | 0.51 | 10.5 |
| 8000 | 7.7 | 40 | 0.47 | 10.5 | |||
| 10000 | 9 | 48 | 0.47 | 10.5 | |||
| 12500 | 10.7 | 56 | 0.47 | 10.5 | |||
| 16000 | 12.9 | 69 | 0.44 | 10.5 | |||
| 20000 | 15.4 | 84 | 0.44 | 10.5 | |||
| 25000 | 18.2 | 99 | 0.41 | 10.5 | |||
Isiguquli samandla esiNgqondileyo se-110KV esineMigangatho emithathu esiNgqondileyo
| Umthamo olinganisiweyo (kVA) | Indibaniselwano yeVoltage kunye noluhlu lweTap | Ukudibanisa Ileyibhile yeqela | Akukho mthwalo ilahleko kW(9) | Umthwalo ilahleko kW(9) | Akukho mthwalo i-% yangoku | Intambo emfutshane ukuthintela % | |
| I-voltage ephezulu (kV) | I-voltage ephantsi(kV) | ||||||
| 31500 | 110±8×1.25% | 6.3 | YNd11 | 21.6 | 117 | 0.41 | 10.5 |
| 40000 | 6.6 | 25.8 | 148 | 0.37 | 10.5~18 | ||
| 50000 | 10.5 | 30.6 | 184 | 0.37 | |||
| 63000 | 21 | 36.3 | 220 | 0.34 | |||
Phawula:
1. I-transformer elawula umthwalo, ibonelela ngemveliso yesakhiwo seenkunzi okwethutyana.
2. Ngokweemfuno zomsebenzisi, ingabonelela ngezinye iimveliso zokudibanisa i-voltage.
Indawo yokuthepha eyi-3.-10% yeyona pompo iphezulu yamandla.
4. Xa isantya somthwalo sonyaka se-transformer siphakathi kwe-45%-50%, ixabiso lokulahleka kwitheyibhile lingasetyenziselwa ukufumana ukusebenza kakuhle okuphezulu.
Isiguquli samandla esilawula iVolthi esingamaPhase amaThathu esinamavili amabini esi-110KV
| Umthamo olinganisiweyo (kVA) | Indibaniselwano yeVoltage kunye noluhlu lweTap | Iqela elidibanisayo Ileyibhile | Akukho mthwalo ilahleko kW(9) | Ukulahleka komthwalo kW(9) | Akukho mthwalo i-% yangoku | Impedance yesekethe emfutshane % | ||
| I-voltage ephezulu (kV) | I-voltage ephakathi (kV) | I-voltage ephantsi(kV) | ||||||
| 6300 | 110±8×1.25% | 36 37 38.5 | 6.3 6.6 10.5 21 | YNyn0d11 | 7.70 | 42.0 | 0.61 | Iphakathi kakhulu (10.5) Iphezulu-ephantsi (18~19) Ephakathi-ephantsi (6.5) |
| 8000 | 9.20 | 50.0 | 0.61 | |||||
| 10000 | 10.9 | 59.0 | 0.57 | |||||
| 12500 | 12.9 | 70.0 | 0.57 | |||||
| 16000 | 15.4 | 86.0 | 0.54 | |||||
| 20000 | 18.2 | 101 | 0.54 | |||||
| 25000 | 21.6 | 120 | 0.50 | |||||
| 31500 | 25.7 | 142 | 0.50 | |||||
| 40000 | 30.8 | 170 | 0.46 | |||||
| 50000 | 36.4 | 202 | 0.46 | |||||
| 63000 | 43.3 | 243 | 0.42 | |||||
Phawula:
1. I-transformer elawula umthwalo, ibonelela ngemveliso yesakhiwo seenkunzi okwethutyana.
2. Ukwabiwa kwamandla okujika kombane ophezulu, ophakathi nophantsi yi (100/100/100)%.
3.Ileyibhile yeqela loqhagamshelwano ingaba yi-YNd11y10 ukuba kuyimfuneko.
4. Indawo yokuthepha ye--10% yeyona pompo iphezulu yamandla.
5. Ngokweemfuno zomsebenzisi, i-voltage ephakathi ingakhethwa ukuba yahluke kwixabiso le-voltage etafileni okanye usete i-tap.
6. Xa isantya somthwalo sonyaka se-transformer simalunga ne-47%, ixabiso lokulahleka kwitheyibhile lingasetyenziselwa ukufumana ukusebenza kakuhle okuphezulu.
Isiguquli samandla soLawulo lweVolthi yoMthwalo esineeNqanaba eziThathu se-110KV esikrelekrele
I-6300kVA-63000kVA enezigaba ezintathu eziphindwe kabini ezijikelezayo ezine-voltage ephantsi eyi-35kV
| Inikwe ingqikelelo umthamo (kVA) | Indibaniselwano yeVoltage kunye noluhlu lweTap | Ukudibanisa iqela Ileyibhile | Akukho mthwalo ilahleko kW(9) | Ukulahleka komthwalo kW(9) | Akukho mthwalo i-% yangoku | Intambo emfutshane ukuthintela % | |
| I-voltage ephezulu (kV) | Iphantsii-voltage(kV) | ||||||
| 6300 | 110±2×2.5% 115±2×2.5% 121±2×2.5% | 36 37 38.5 | YNd11 | 6.40 | 35.0 | 0.54 | 10.5 |
| 8000 | 7.70 | 42.0 | 0.54 | ||||
| 10000 | 9.0 | 49.0 | 0.50 | ||||
| 12500 | 10.5 | 59.0 | 0.50 | ||||
| 16000 | 12.5 | 72.0 | 0.46 | ||||
| 20000 | 14.8 | 89.0 | 0.46 | ||||
| 25000 | 17.5 | 105 | 0.42 | ||||
| 31500 | 20.7 | 126 | 0.42 | ||||
| 40000 | 24.6 | 147 | 0.39 | ||||
| 50000 | 29.5 | 183 | 0.39 | ||||
| 63000 | 34.9 | 220 | 0.36 | ||||
Phawula:
Indawo yokuthepha eyi-1.-10% yeyona pompo iphezulu yamandla
2. Kwi-boost transformer, kufanelekile ukusebenzisa isakhiwo esingenampompi. Ukuba kuyimfunekoumsebenzi, itephu ingamiselwa.
3.Xa umthwalo wonyaka oqhelekileyo we-transformer uphakathi kwe-44%-47%, ixabiso lokulahleka kwitheyibhile lingasetyenziselwa ukufumana ukusebenza okuphezulu.
Isishwankathelo sokugqibela:
1. Amaxabiso okulahleka komthwalo kuzo zonke iitheyibhile zeeparameter ezingentla ziiparameter zeChinese National Standard type 18. Inkampani yethu ingazilungiselela ngokweemfuno zabasebenzisi.
2. Ngokweemfuno zomsebenzisi, ingavelisa iimveliso ezingaphandle komthamo wetafile, iiparameter zayo zokusebenza zixhomekeke kwiimfuno.
3. Ngokweemeko zokusebenza ezahlukeneyo, singabonelela ngeemveliso ezilungiselelwe ngokukodwa.
4. I-voltage ephakathi ingakhethwa ukuba yahluke kwixabiso le-voltage etafileni okanye kwi-tap, i-tap yoxinzelelo oluphezulu ukuze ukhethe i-tap yokulawula i-voltage engalinganiyo.
5. Impedance yesekethe emfutshane inokukhethwa eyahlukileyo kwixabiso eliphakathi kwetafile.
6. Ubungakanani bokugqibela buya kuxhomekeka ekuqinisekisweni komzobo emva kokuba isivumelwano sisayiniwe.
● I-110kV enezigaba ezintathu eziphindwe kabini ezijikelezayo kwi-voltage yokulawula umbane
● Iinkcukacha ezahlukeneyo zee-power transformers zingaphuhliswa ngokweemfuno ezikhethekileyo zabasebenzisi.